Name:Dixell water chiller and heat pump controller IC208CX-11000
Brand:Dixell
Model No.:IC
Part No.:IC208CX-11000
Country of origion:China
Voltage:12/24VAC/DC
Real Time Clock:Optional

Product Description

Dixell water chiller and heat pump controller IC208CX-11000


Dixell - IC208CX-11000 + BUZ EVO 24V MULTIFUNCTION CONTROLLER, FOR CHILLERS, HEAT PUMPS, 12/24VAC/DC, 8 RELAY OUTPUTS, 1 OR 2 CIRCUIT UP TO 4 STEPS, NO REALTIME CLOCK(RTC)



Advanced Multifunction Controller for Chiller applications

This IChill IC208CX advanced multifunction controller provides simple management and control of chillers, heat pumps and geothermal heat pump units (with solar integration and sanitary hot water production) with single or dual circuits gas and water reversibility and up to four steps. This advanced controller designed for chiller unit applications with one or two circuits, such as air/air, air/water, motor-condensing.

Includes a vibrant colour dual 4 digit display, a 6 pushbutton keyboard for simple set-up, 6 configurable probe inputs, 11 configurable digital inputs, 6 relay outputs, EEPROM memory and an accuracy of plus or minus 0.7 deg C. With combined/forced defrosting, alarm control, screw compressor management, compressor management through inverter, direct, part-winding, star-delta compressor start.

This temperature controller is also suitable for the management of solar panels, sanitary hot water production, heat recovery management, free-cooling management.

Multifunction Controller Features

Power supply 12, 24Vac/dc

Probe inputs NTC, PTC - 6 x configurable

Digital inputs Free voltage - 11 x configurable

Relay outputs 5A - 6 x configurable

Serial output TTL

LAN output

Remote display output

Display 4 digits, red LED 8.5mm high, 4 digits, yellow LED 7.5mm high

Non-volatile memory (EEPROM)

Operating temperature-10÷55°C

Relative humidity 20÷85% (no condensing)

Resolution 0.1°C 0.1 bar

Features

Management of scroll, screw and inverter compressors

Identification of the compressors to activate based on the n° of hours/start-ups

Data logger up to 100 alarms (alarm type, date, hours, machine status)

Solar panel management

Dynamic set point

Heat recovery management

Free-cooling management

Pump-down function (stop and start)

Capacity function of machine power during critical functioning conditions

Forced defrost during critical conditions

Combined defrost temperature/pressure

Sanitary hot water production

Specifications

Analogs:2 X PWM/0÷10V, 2 x 0÷10V

Buzzer:Present

Digital Inputs:Free voltage: 11 x configurable

Display:Dual with icons

Hot Key 64:Present

LAN Output:Present

Power Supply:12, 24Vac/dc

Probe Inputs:NTC, PTC: 4 x configurable - NTC, PTC, 4÷20mA, 0÷5V: 2 x configurable

Prog Tool Kit Output:Present

Real Time Clock:Optional

Relay Outputs:5A: 8 x configurable

Remote Display Output:2 X VICX620, 1 x V2I820, 1 x VTIC20

TTL Output:Present